Environment Monitoring System Temperature/Humidity Sensors

Environmental Sensors compatible with ENVIROMUX-16D

Temperature/Humidity Sensors

Temperature/Humidity Sensor

ENVIROMUX-STHS Temperature Sensor/Humidity Sensor
ENVIROMUX-STHS
  • Applications from 32 to 122°F (0 to 50°C) and 20 to 80% relative humidity.
  • Accurate to within ±0.9°F (±0.5°C) and ±5% relative humidity.
  • High resistance to external influences on the cable due to digital output signal.
  • RJ45 connector.
  • Voltage Supply: 5VDC
  • Current Consumption: 20mA
  • Communication type: RS485
  • Data rate: 96kbps
  • Supports CAT5/5e/6/6a cable (24 AWG) up to 1,000 ft (305 m) (not included).
  • Powered by ENVIROMUX-2D/5D/16D.
  • Compatible with ENVIROMUX-2D/5D/16D.
  • Regulatory approvals: CE, RoHS
  • Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
NTI Part # Quote
ENVIROMUX-STHS

Temperature/Humidity Sensor with Two Digital Inputs

ENVIROMUX-STHS Temperature Sensor/Humidity Sensor
ENVIROMUX-STHSD
  • Applications from 32 to 122°F (0 to 50°C) and 20 to 80% relative humidity.
  • Accurate to within ±0.9°F (±0.5°C) and ±5% relative humidity.
  • RJ45 connector.
  • Voltage supply: 5VDC.
  • Communication type: RS485.
  • Digital inputs support up to two dry contact sensors.
    • DC power has to be provided separately.
  • Power consumption:
    • +5V Rail: 4.9V.
    • DC current: 13mA.
  • Supports CAT5/5e/6/6a cable (24 AWG) up to 1,000 ft (305 m) (not included).
    • Digital inputs support 22-AWG sensor cables to 1,000 ft (305 m).
    • Cables not included.
  • Compatible with ENVIROMUX-2D/5D/16D.
    • ENVIROMUX-2D: only compatible with Rev C units (features two power inputs).
    • Not compatible with ENVIROMUX-SEMS-16(U).
  • Regulatory approval: CE, RoHS.
  • Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
NTI Part # Quote
ENVIROMUX-STHSD

Dry Contact Sensors Compatible with ENVIROMUX-STHSD


Temperature/Wide Range Humidity Sensor

ENVIROMUX-STHS-99 Temperature/Wide Range Humidity Sensor
ENVIROMUX-STHS-99
  • Applications from 32 to 176°F (0 to 80°C)
  • Accurate to within ±2°F (0 to 50°C, ±1°C)
    • 20 to 80% relative humidity, ±3%
    • 10 to 90% relative humidity, ±4%
    • 0 to 99% relative humidity, ±5%
  • Supports dew point measurement.
  • High resistance to external influences on the cable due to digital output signal.
  • Re-calibration is not necessary after initial set-up.
  • RJ45 connector.
  • Supports CAT5/5e/6/6a cable (24 AWG) up to 1,000 ft (305 m) (not included).
  • Powered by ENVIROMUX-2D/5D/16D
  • Regulatory approvals: CE, RoHS
  • Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
NTI Part # Quote
ENVIROMUX-STHS-99

Low-Cost Precision Temperature/Humidity Sensor, 32 to 140°F (0 to 60°C)

Low-Cost Precision Temperature/Humidity Sensor
ENVIROMUX-STHS-PRC
  • Applications from 32 to 140°F (0 to 60°C) and 10 to 80% relative humidity.
  • Accurate to within ±0.4°F (±0.2°C) and ±1.8% relative humidity.
  • Supports dew point measurement.
  • High resistance to external influences on the cable due to digital output signal.
  • RJ45 connector.
  • Voltage Supply: 5VDC
  • Current Consumption: 20mA
  • Communication type: RS485
  • Data rate: 96kbps
  • Supports CAT5/5e/6/6a cable (24 AWG) up to 1,000 ft (305 m) (not included).
  • Powered by ENVIROMUX-2D/5D/16D.
  • Compatible with ENVIROMUX-2D/5D/16D.
    • ENVIROMUX-2D: only compatible with Rev C units (features two power inputs).
  • Regulatory approvals: CE, RoHS
  • Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
Downloads & References

NTI Part # Quote
ENVIROMUX-STHS-PRC

Wall Mount Temperature/Humidity Sensor

Wall Mount Temperature/Humidity Sensor
ENVIROMUX-STHS-WLM
  • Combines excellent stability with easy installation and reliable operation.
  • Applications from 23 to 131°F (-5 to 55°C)
  • Temperature accurate to within ±0.9°F (±0.5°C)
  • Relative Humidity accuracy:
    • ±3% from 30 to 70% relative humidity.
    • ±5% from 0 to 30% and 70 to 100% relative humidity.
  • Requires the ENVIROMUX-S420MA-24V to operate.
    • Maximum cable length: 500 ft (152 m).
    • Powered by ENVIROMUX-2D/5D/16D.
  • Regulatory Approvals: CE, RoHS
  • Enclosure: IP30
  • Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
Downloads & References
NTI Part # Quote
ENVIROMUX-STHS-WLM
ENVIROMUX-S420MA-24V